APP Propane operates a fleet of modern boom trucks equiped with powerful lifting booms

to allow for placing a propane tank in those hard to reach or sensitive locations. APP offers

a "no charge tank swap out" program to facilitate swapping up to APP service and cost

saving opportunities.

Federal, state, and local ordinances and regulations should be observed at all times.

|
  |
 |

Notes:
1. Regardless of its size, any ASME tank filled on-site must be located so that the filling connection
and fixed liquid level gauge are at least 10 feet from external source of ignition (i.e. open flame,
window A/C, compressor, etc.), intake to direct vented gas appliance, or intake to a mechanical
ventilation system.

2. May be reduced to 10 feet minimum for a single container of 1200 gallon water capacity or
less if it is located at least 25 feet from any other LP-Gas container of more than 125 gallon
water capacity.

3. Minimum distances from underground containers shall be measured from the relief valve and
filling or level gauge vent connection at the container, excpet that no part of an underground
container shall be less than 10 feet from a building or line of adjoining property which may
be built upon.

4. Where the container may be subject to abrasive action or physical damage due to vehicular
traffic or other causes it must be either: a) placed not less than 2 feet below grade, or b) otherwise
protected against such physical damage.
|
 |
 |